Page 250 SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS A5E33329501
mmmmm
Technical Data
Source
Integral transducer sensor
TS-3 temperature sensor
Average (integral transducer and TS-3)
Programmable fixed temperature
Temperature Error
Fixed
0.17 % per °C deviation from programmed value
Memory
512 kB flash EPROM
1.5 MB flash for data logging
Interface
Outputs
mA Analog
4-20 mA
600 ohms maximum in ACTIVE mode, 750 ohms maximum in PASSIVE mode
Resolution of 0.1%
•Isolated
Relays
1
(3)
•2 control
1 alarm control
Control Relays
2 Form A (SPST), NO relays
Rated 5A at 250 V AC, non-inductive
Rated 3A at 30 V DC
1.
All relays are certified only for use with equipment that fails in a state at or under the rated
maximums of the relays.