Page 42 SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS 7ML1998MV01
mmmmm
Commissioning
Low Calibration Point
Distance from Sensor Reference Point to Low Calibration Point: usually process
empty level.
Response Rate
Sets the reaction speed of the device to measurement changes in the target range.
Use a setting just faster than the maximum filling or emptying rate (whichever is
greater). Slower settings provide higher accuracy, faster settings allow for more
rapid level fluctuations.
End of QS Level Wizard
For QS to be successful, all changes must be applied.
To transfer Quick Start values to the device and return to Program menu, press
DOWN arrow (Finish). Then press LEFT arrow three times to return to
Measurement mode.
Value
Range: 0.000 to 60.000
Default: 60.000
Notes:
• Response Rate can only be set through the Quick Start Wizard, and any
changes made to Fill Rate per Minute (2.3.1.), Empty Rate per Minute (2.3.2.), or
Damping Filter (2.3.3.) parameters following the completion of the wizard will
supersede the Response Rate setting.
• Response Rate always displays in m/minute.
Options
SLOW (0.1 M/MIN)
MEDIUM (1.0 M/MIN)
FAST (10 M/MIN)
Default: SLOW (0.1 M/MIN)
Options
BACK, CANCEL, FINISH
(Display returns to 1.1 Quick Start menu when Quick Start is successfully com-
pleted or cancelled. If CANCEL is selected, no changes are written to the
device.)