Page 74 SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS A5E33329501
mmmmm
General Operation
2. Enter the curve values from this chart into level and volume breakpoint tables (see
2.6.7. Table 1-8
).
3. Ensure extra points are added around sharp transitions in the vessel volume (e.g:
steps in a well wall).
Example chart (with 15 of possible 32 Level and Volume breakpoints defined):
Note: If breakpoints are entered via LUI, then an upload is performed via PDM, a
second upload via PDM may be necessary to transfer the breakpoint values.
Note: The end points in the curve are 0,0 (fixed) and the point defined by
Maximum Level and Maximum Volume.
Parameter Value Description
2.6.7.1. Level 1
0.0
Determines the Level breakpoints at which
the volumes are known.
Level 2 0.8
Level 3 2.0
Level 4 3.5
Level 5 4.1
Level 6 4.7
Level 7 5.1
Level 8 5.2
Level 9 5.3
Level 10 5.4
Level 11 5.5
Level 12 5.6
Level 13 6.0
Level 14 7.2
Level 15 9.0
LEVEL
Breakpoints
0,0
VOLUME Breakpoints
MAX VOLUME
MAX LEVEL