A5E33329501 SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS Page 171
mmmmm
Parameters
2.9.1. Backup Level Override
Use this feature to override the material reading by a discrete input such as a
contacting point device. The material reading will be fixed at the programmed
switch level until the discrete input is released. The LUT400 makes decisions
based on the override values.
2.9.1.1. Enable
Enables/disables the Backup Level Override function.
2.9.1.2. Level Override Value
This value is substituted for the current reading when the selected discrete
input is enabled and ON.
Value is defined in current
2.1.1.Units
, and is valid only for level (and head
when
2.1.2.Sensor Mode
set to Flow). (Volume is calculated based on the
Backup level.)
2.9.1.3. Discrete Input Number
Sets the discrete input to act as the source for a level reading override
when enabled.
Options
ENABLED
*
DISABLED
Values
Range: 0.000 to 60.000
Default: 0.000
Options
*
DISCRETE INPUT 1
DISCRETE INPUT 2