A5E33329501 SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS Page 237
mmmmm
Troubleshooting
Symptom Cause Action
Reading fluctuates
while material level is
still
Material level is changing Visually verify, if possible.
Strong false echoes Determine source of false echoes;
Relocate transducer to avoid
source.
Incorrect damping Adjust damping. See Damping Fil-
ter (2.3.3.) on page 143.
Improper echo Algorithm selec-
tion
Set algorithm to default. If no
improvement, try a different algo-
rithm. See Algorithm (2.12.2.1.) on
page 182.
High noise levels Verify source and minimize. See
“Noise Problems” on page 242.
Weak echo Determine cause;
Check noise, confidence, FOM,
and echo strength. See Echo
Quality (3.2.9.) on page 204.
Foam on surface of material Eliminate source of foaming;
Use stilling well.
Rapid temperature changes Use an external temperature sen-
sor. See Temperature Source
(2.12.1.3.) on page 181.
Faulty temperature sensor Verify operation;
Replace if required, or use fixed
temperature. See Temperature
Source (2.12.1.3.) on page 181.
Vapours If fluctuation is unacceptable, con-
sider an alternative technology.
Contact your Siemens representa-
tive.