1 Probable Cause
1 Corrective Action
. A remote annunciator’s RESET
or SILENCE switch not in the
normal postion
l
Transformer connection P4 not
l
Open card supervisory loop
Restore to normal position.
Connect the transformer cable
rconnecting harnesses
l
Battery fuse F3 open
nections are not
Replace F3 (8 amp) fuse.
# 8. Both “SYSTEM TROUBLE” and one
or more “SIGNAL” Trouble LEDs
are on
from circuit (bell, horn,
AN uni
0 Open connection on signal circuit
- Repair the open line condition.
(The E.O.L. resistor’s 1 OK ohms
should be read between the signal
l
Electrical short in signal circuit
- Repair the short circuit condition.
(The E.O.L. resistor’s 10K ohms
should be read between the signal
EM TROUBLE” and CITY
TROUBLE LEDs are on
. CITY BYPASSswitch not in its
normal position
l
Configuration jumpers incorrectly
set
Set jumper correctly.
l
Open in city circuit field wiring
- Repair the open line condition.
# 8. Both “SYSTEM TROUBLE” and
“GROUND TROUBLE” LEDs are on
One or more conductors are shorted
to ground
* Remove field wiring from connector:
one pair at a time until
ground fault clears.
# 9. Both “SYSTEM TROUBLE” and
“ANNUN TROUBLE” LED’s are on
l
Burned out LED in annunciator
l
Open connection between panel
and annunciator
* Depress SYSTEM RESET to check
annunciator LEDs.
* Repair open line condition.
l
Serial annunciator not installed
in system
Set SW3 to all closed positions.
l
DIP switch SW3 settings incorrect
0 DIP switch SW1 1 settings incorrect
Set SW3 to indicate correct number of
senal annunciators in system.
Set SW1 1 to indicate correct number
of supervised annunciators. See Wire
Diagrams.
l
Defective annunciator
l
Defective module in fire alarm panel
Call Simplex
Call Simplex
13
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4002

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4002 and is the answer not in the manual?

Simplex 4002 Specifications

General IconGeneral
Voltage24 VDC
Temperature Range32°F to 120°F (0°C to 49°C)
Humidity RangeUp to 93% RH, non-condensing
Interconnect CapabilityYes
ComplianceUL

Related product manuals