4002 PANEL DISPLAYS
NORMAL, TROUBLE AND ALARM CONDITIONS
l
Normal Condition
- Green “POWER ON” LED on.
- All other panel indicators off.
0 Trouble Condition
- System Trouble buzzer sounds continually.
- One or more amber “TROUBLE” LEDs on.
0 Alarm Condition (Non-ESP)
- All signals sound.
- AUX and city relays activate.
- One or more “ALARM” LEDs flash.
- System trouble buzzer sounds at a march time cadence (120 pulses per minute).
Note:
The following Software functions will affect the ALARM SILENCE operation.
a.
Selective coded station input
- Indicating appliances cannot be silenced when zone 1 is in alarm. The
indicating appliances will be silenced automatically when coding is complete. The flashing zone LED
will change to a steady state when the code is completed.
b.
Waterflow Sprinkler On
Zone 7 - Indicating appliances cannot be silenced if water is flowing in the
sprinkler system.
c.
Alarm Silence inhibit
- Programmed for 1, 3, or 5 minutes.
d.
Signal
Cutoff - After 10 minutes of continuous operation, signals silence autom&aiiy.
l
Signals can be manually silenced at any time.
OPERATING 4002 OPTIONAL EQUIPMENT
l
ESP Programming Option (See Appendix A)
- System programmed to meet customer requirements.
- Provides 23 additional functions.
l
Fan Control Module (See Appendix B)
- Provides hand/OFF/automatic (HOA) operations for climate and smoke control.