d. Selective Door Holder Reiay Control
One or more selected monitor point inputs will act upon one or more relay circuits which control door holder
circuits.
e. Selective Bypass Control Switch Operation
One or more selected inputs (monitor or control) will selectively bypass control circuits.
f. Selective Switch Operation
One or more selected switch inputs will selectively control output circuits.
g. Multiple Tamper Zones
One or rhore selected monitor point inputs (connected to sprinkler gate valves, N/O or N/C) which activate
specific tamper signals.
h. Stage l/Stage 2 Operation or Presignal Operation
Stage l/Stage 2 -
Zone activation alerts in-house personnel and starts a delay timer. If the timer is not
reset before the delay expires, evacuation signals sound automatically.
Presignal -
Zone activation alerts in-house personnel. A second (manual) action is required before
evacuation signals sound.
i. Cross Zoning
A method of operation by which two or more monitor points must be activated before an output action can
occur.
j. Timing Functions
One or more selected monitor point inputs may cause a selected output to activate fur a predetermined time
period or after a time period elapses.
k. Master Code
One or more selected monitor point inputs will cause a selected coded pulse pattern to be outputted to
selected control outputs. (Usually the notification appliance circuits or city circuit).
I. Non-Alarm Monitor Point Operation
A method of removing one or more selected monitor points from the 4002 general alarm program. The
monitor point alarm LED will flash when activated, but no control outputs will occur unless specified in an
E.S.P. equation.
M.
Non-latching Monitor Point
OperatiOn
A method of allowing one or more selected monitor point to “track” a peripheral device contact closing or
opening.
l
Only non-alarm contacts should be non-latching.
n. Piezo Signal Operation
The ability to control the Piezo selectively using any function statement in E.S.P.
o. AC Power Fail (Control)
The ability to control any output during an AC power loss or brownout condition at the 4002 panel.