4002 FIRE ALARM SYSTEM OPERATING INSTRUCTIONS
FOLLOWING AN ALARM/TROUBLE CONDITION
YOUR SAFETY AN0 THE SAFETY OF THOSE AROUND YOU
ALWAYS COMES FIRST!
g a fire depend upon lee01 practices. Be sure
HOW TO OPERATE THE PANEL DURING AN ALARM SITUATION:
l
Identify the zone in alarm via the control panel indicators. Follow Local Procedure to investigate that zone to
determine the cause of the alarm. (Pull station activated, smoke detector activated etc.)
l
After all occupants are evacuated, unlock and open the panel door.
l
To silence signals, press the alarm silence push button.
- Audible signals are silenced, alarm silenced LED illuminates, and any red zone indicator that was flashing
comes on steady. If another alarm is reported from another zone, the alarm signals sound again, the alarm
silenced LED turns OFF, and the red indicator representing the zone in alarm flashes until the audible signals
are again silenced.
HOW TO RESET THE FIRE ALARM SYSTEM FOLLOWING AN ALARM CONDITION:
l
When the alarm situation has been cleared, restore or replace all affect& alarm-initiating devices (pull stations
and detectors) in accordance with the instructions provided with each device.
l
Press and hold the SYSTEM RESET switch until LEDs illuminate (see Note below).
- The trouble buzzer sounds for 2 seconds and LEDs illuminate for approximately 5 seconds.
WHAT TO DO IN CASE OF TROUBLE:
l
Notify appropriate personnel.
NAME
ADDRESS
PHONE
NUMBER
l
Unlock and open panel door.
l
If tone device is sounding, press the trouble silence push button.
l
Refer to the 4002 Customer Instructions manual for additional instructions or call a local Simplex Branch Office
for assistance.
Note: The following options affect the system as follows:
l
Waterflow/Sprinkler - you cannot silence an alarm or reset the system if water is flowing in the
sprinkler system.
l
Coded Input On Zone 1 -the signals cannot be silenced while a code is being transmitted.
l
ESP (Expanded Simplex Programming)
l
Silence Inhibit - you cannot silence an alarm or reset the system until the specified time period has
elapsed.
0 Custom Project Specific Software Programming
THESE INSTRUCTIONS ARE INTENDED TO BE FRAMED AND MOUNTED ADJACENT TO THE
CONTROL PANEL FOR READY REFERENCE.
__--- -_-------------
------
Refer to the Customer’s Instructions for a detailed description of system operation.
4
7
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4002

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4002 and is the answer not in the manual?

Simplex 4002 Specifications

General IconGeneral
BrandSimplex
Model4002
CategorySmoke Alarm
LanguageEnglish

Related product manuals