Page #44 background imageLoading...
Page #44 background image
CHART 2
IF END VOLTAGE READING OF BAlTERY IS:
INSTRUCTIONS
11
.av
or more
Put in Service
11.7v to ll.OV
Charge Battery
l
Discard Battery
10.9 or less
l
Retest battery after charging.
Note 1:
Discard if battery has been in service for four or more years (dispose of properly).
Note
2: Dispose of properly.
42
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4002

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4002 and is the answer not in the manual?

Simplex 4002 Specifications

General IconGeneral
Voltage24 VDC
Temperature Range32°F to 120°F (0°C to 49°C)
Humidity RangeUp to 93% RH, non-condensing
Interconnect CapabilityYes
ComplianceUL

Related product manuals