Acknowledging an Alarm, Continued
Globally
Acknowledging
Alarms
Use the following procedure if the Global Acknowledge option is enabled on your 4010ES system.
1. Unlock and open the enclosure door. Read the alphanumeric display on the interface panel. It
reports the number of alarm conditions as shown below.
2. Press the FIRE ALARM ACK key. Read and follow the instructions on the alphanumeric display.
After you press the FIRE ALARM ACK key, the system responds as follows:
The tone-alert silences and the alphanumeric display reports pertinent information about the
alarm, such as the following:
The ALARMS LED changes from flashing to steady ON, and all alarm conditions are
acknowledged.
Pressing the FIRE ALARM ACK key again displays information on the next alarm.
Continue to do this to review all alarms in the system.
Individually
Acknowledging
Alarms
Use the following procedure if the Individual Acknowledge option is enabled on your 4010ES
system.
1. Unlock and open the enclosure door. Read the alphanumeric display on the interface panel. It
reports the number of alarm conditions as shown below.
2. Press the FIRE ALARM ACK key. A report similar to the one shown below appears. Read and
follow the instructions on the alphanumeric display.
Continued on next page

Table of Contents

Other manuals for Simplex 4010ES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4010ES and is the answer not in the manual?

Simplex 4010ES Specifications

General IconGeneral
Control Panel TypeAddressable Fire Alarm Control Panel
DisplayLCD
Operating Temperature32°F to 120°F (0°C to 49°C)
Power Supply120V AC or 240V AC
Zones10
Communication PortsRS-232, Ethernet
Signaling Line Circuits (SLCs)2
Notification Appliance Circuits (NACs)4
Max Notification AppliancesVaries based on NAC configuration and power supply
Communication OptionsCellular, Ethernet
Weight30 lbs
Humidity RangeUp to 93% non-condensing
CertificationsUL, FM, CSFM, MEA
Network CapabilityYes

Related product manuals