7-6
TrueNAC Voltage Drop Test, Continued
Accessing the
TrueNAC Voltage
Drop Test
2. Press the Next key on the Display/Action keypad. Use the Next and Previous keys to scroll to the
Diagnostic Functions. The following message displays:
3. Press the ENTER key on the Entry keypad. Scroll to the TrueNAC Voltage Drop Test using the
Next and Previous keys on the Display/Action keypad. The following message displays:
4. Press the ENTER key on the Entry keypad. The following message displays.
Testing all
TrueAlert Power
Supply’s SLCs
Use the following procedure to test all the TrueAlert Power Supply’s SLC lines at once. Before you
start this test, make sure you have already completed the procedure Accessing the TrueNac Voltage
Drop Test.
1. Press the ENTER key on the Entry keypad. The following message displays:
2. To turn the horn on or off before performing the TrueNAC Voltage Drop Test, use the Next and
Previous keys to set the horn state.
Note: The horn can be turned off to prevent any disturbance during the TrueNAC Voltage Drop Test.
Horns that are turned on are set to high volume. If Horns are on, the panel will perform two
passes one with horns on and one with horns off. This is done to enhance measurement
accuracy with A/Vs.
Continued on next page

Table of Contents

Other manuals for Simplex 4010ES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4010ES and is the answer not in the manual?

Simplex 4010ES Specifications

General IconGeneral
Control Panel TypeAddressable Fire Alarm Control Panel
DisplayLCD
Operating Temperature32°F to 120°F (0°C to 49°C)
Power Supply120V AC or 240V AC
Zones10
Communication PortsRS-232, Ethernet
Signaling Line Circuits (SLCs)2
Notification Appliance Circuits (NACs)4
Max Notification AppliancesVaries based on NAC configuration and power supply
Communication OptionsCellular, Ethernet
Weight30 lbs
Humidity RangeUp to 93% non-condensing
CertificationsUL, FM, CSFM, MEA
Network CapabilityYes

Related product manuals