D-6
This option simply displays the last Earth Fault Search result. If there has been no search
since the last system startup, or if the last search was aborted, the panel displays
"RESULT NOT AVAILABLE."
When a Location or IDNet Channel Search completes, all of the following occurs:
All slaves automatically reset.
The FIP turns off the Earth Fault Search trouble pseudo-point.
The panel displays the specific fault information.
The panel can return only one Earth Fault Search result at a time. If another fault exists, it
can be found only via diagnostics after the first fault is cleared. Faults will continue to
appear, one by one, until each one has been found and corrected.
IMPORTANT: Once you have been directed to an earth ground fault and
corrected it, it is recommended that you restart the system (warm- or cold-
start). Refer to the InfoAlarm Operator Manual for details of how to do this.
Earth Fault Searching from the Front Panel, Continued
Last Search Result
Completing the
Search