1-7
AZF Alarm Zone Facility – means of grouping multiple detectors or devices,
and providing common indication and control.
Class A Wiring Method of connecting multiple devices or units in a loop. This requires
up to twice as much wire but means that a short or open circuit in any
one section will not prevent communication with every device.
Class B Wiring Connection of multiple devices sequentially, or with spurs, uses the
minimum amount of cable, but a single wiring fault can affect all
devices at once.
FIP Fire Indicator Panel – usually abbreviated to “panel”.
GPO General Power Outlet – mains power socket.
IDNet Individual Device Network – latest generation of Simplex analogue
addressable devices and the 2-wire loop that connects them.
InfoAlarm Graphic LCD user interface. Sometimes referred to as a FUI (Flexible
User Interface). Up to six InfoAlarm units can be connected to a
4100ES FIP.
MAPNet Multi-Application Peripheral Network – an earlier version of
addressable device communication superseded by IDNet. Some
MAPNet devices can be used on IDNet loops.
NAC Notification Appliance Circuit – switched DC output, usually with
supervision, for powering notification appliances and warning system
devices.
NIC Network Interface Card – provides network communications between
multiple 4100/4100ES panels.
PID Product Identification (part number).
PDI Power Distribution Interface – method of mounting and powering 4100
modules in a bay.
RTU Remote Transponder Unit – remotely located cabinet, containing slave
modules controlled by a 4100ES master panel.
RUI Remote Unit Interface – 2-wire communications loop used to connect
4100/4100ES master panels with remote transponders.
SPS System Power Supply – the main 4100ES power supply and battery
charger module. Also includes an IDNet loop, three NAC outputs, and
the brigade relay card.
Glossary

Table of Contents

Other manuals for Simplex 4100ES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100ES and is the answer not in the manual?

Simplex 4100ES Specifications

General IconGeneral
TypeFire Alarm Control Panel
DisplayLCD
Battery BackupYes
Model4100ES
ManufacturerSimplex
Communication ProtocolOptional Ethernet
Signaling Line Circuits (SLCs)Up to 10
Notification Appliance Circuits (NACs)Up to 10
Agency ListingsUL, FM, CSFM, MEA
Max Relay Circuits20
Communication PortsEthernet
Operating Temperature32°F to 120°F (0°C to 49°C)
HumidityUp to 93% RH, non-condensing