3-5
The TIC and all other cards mounted in the transponder cabinet and attached expansion
bays must be configured to operate correctly in the system via their DIP switch and
jumper ports. The CPU motherboard may have to be configured as well.
P9 on the CPU motherboard determines whether the RUI SHIELD signal is connected to
24 C or Earth.
Position 1 – 2: SHIELD to 24 C (default).
Position 2 – 3: SHIELD to Earth.
Note: Some devices that connect to RUI have inherently grounded shield
terminals, in which case 24 C cannot be used. If 24 C is used, a
Negative Ground Fault will occur.
The TIC must be assigned a device address via DIP switch SW1. Refer to Appendix A for
the address switch table.
Refer to the respective installation sheets to configure the other cards that are located in
the transponder cabinet and attached expansion bays.
Configuring Cards (4100ES){xe "transponder interface card (TIC):
configuring"}{xe "card configuration: transponder interface card (TIC)"}
Overview
CPU Motherboard
DIP Switch
TIC Configuration
Configuring Other
Cards