Model
4100-6077AU or 4100-6077LIM
MX Loop output reference
MX Loop output.
Voltage.
40VDC maximum.
Current.
500mA maximum.
Number of addresses.
250 maximum.
4100ESi panel capacity.
Up to 30 4100-6077 MX Digital Loop Cards.
Loop distance.
2000m maximum.
Loop resistance.
150 maximum.
Loop capacitance.
0.2µF maximum.
Loop inductance.
1.5mH maximum,
Module power requirements
Voltage range.
24VDC nominal, supplied from the control panel power supply.
Card power consumption.
30mA for module only.
Signal power.
1200mA maximum, fully loaded at 250 devices; actual current
depends on connected devices and state, for example Sounders
on.