6 Connection SMA Solar Technology AG
56 ClusterController-IA-en-10 Installation Manual
1. Connect the connection cable to the remote terminal (see the manufacturer manual). For this
purpose, trim the unused insulated wires up to the cable shield and note the wire colours.
2. When using the terminal block Analogue current output 1 (AO1), perform the following
steps to connect the connection cable to the six-pole plug:
Release conductor entry 3 using a screwdriver and insert the insulated wire of the single core
into the conductor entry.
Depending on the remote terminal and the pin assignment at the terminal block
Analogue current output 1 (AO1), identify the conductor entries that are required for the
connection of the connection cable.
Release the required conductor entries using a screwdriver and insert the insulated wires into
the conductor entries. Observe the pin assignment.
3. When using the terminal block Analogue current output 2 (AO2), perform the following
steps to connect the connection cable to the six-pole plug:
Release conductor entry 6 using a screwdriver and insert the insulated wire of the single core
into the conductor entry.
Depending on the remote terminal and the pin assignment at the terminal block
Analogue current output 2 (AO2), identify the conductor entries that are required for the
connection of the connection cable.
Release the required conductor entries using a screwdriver and insert the insulated wires into
the conductor entries. Observe the pin assignment.
4. Insert the six-pole plug at terminal X6 into pin row A.
5. On the connection cable, mark the terminal and pin row to which the connection cable is
assigned. For this purpose, use the cable ties with the caption field.
6. On the supplementary sheet for noting the connected devices, note the terminal to which the
remote terminal is assigned.