HRX-OM-Q026-B
Chapter 5 Display and setting of various functions
5.20 Alarm customizing function HRSH Series
5-64
Changing circulating fluid outlet pressure sensor failure Setting and checking
38. Press the [SEL] key once.
The set screen of the circulating fluid pressure sensor failure is displayed on the digital
display.
PV
SV
39. Select the changing of circulating fluid pressure sensor failure from the table below with
[▲] key or [▼] key, and confirm by pressing “SEL”.
Table 5.20-27 List of set value
Set value Explanation
Initial value
(Default setting)
This alarm signal is not detected.
During this setting, the alarm lamp of the
operation display panel will be blinks, lit on
0.5 seconds and off 3 seconds.
Operation continues when this alarm signal is
generated.
Operation is stopped when this alarm signal is
generated.
○
Changing of pump maintenance Setting and checking
40. Press the [SEL] key once.
The set screen of the circulating fluid pressure sensor failure is displayed on the digital
display.
SV
41. Select the changing of pump maintenance from the table below with [▲] key or [▼] key,
and confirm by pressing “SEL”.
Table 5.20-28 List of set value
Set value Explanation
Initial value
(Default setting)
This alarm signal is not detected.
○
Operation continues when this alarm signal is
generated.