HRX-OM-Q026-B
Chapter 5 Display and setting of various functions
5.21 Communication function HRSH Series
5-74
26. Select responce delay time (simple communication protocol) from the table below with
[] key or [] key, and confirm by pressing “SEL”.
Table 5.21-14 List of set value
Set value Explanation
Initial value
(Default setting)
Setting/checking are not available unless the
serial protocol setting is simple
communication protocol.
to
Setting of response delay time.
Set range is 0 to 250m sec.
Communication range (simple communication protocol) Setting and checking
27. Press the [SEL] key once.
The set screen of communication range (simple communication protocol) is displayed
on the digital display.
PV
SV
28. Select communication range (simple communication protocol) from the table below with
[] key or [] key, and confirm by pressing “SEL”.
Table 5.21-15 List of set value
Set value Explanation
Initial value
(Default setting)
Setting/checking are not available unless the
serial protocol setting is simple
communication protocol.
Only reading is available
Reading and writing are available
Contact input signal 1 Setting and checking
29. Press the [SEL] key once.
The set screen of contact input signal 1 is displayed on the digital display.
PV
SV