HRX-OM-Q026-B
Chapter 5 Display and setting of various functions
HRSH Series 5.21 Communication function
5-75
30. Select contact input signal 1 from the table below with [] key or [] key, and confirm
by pressing “SEL”.
Table 5.21-16 List of set value
Set value Explanation
Initial value
(Default setting)
Without signal input
Start and stop signal input
External switch signal input(N.O. type)
4,
5
External switch signal input (N.C. type)
4,
5
4When the setting of the communication mode is “DIO mode”, “External switch signal” cannot
be set.
5When the setting of the communication mode is “SEIRAL mode” and the protocol setting is
“Simplified communication protocol 2”, “External switch signal” cannot be set.
Contact input signal 1 type Setting and checking
31. Press the [SEL] key once.
The set screen of contact input signal 1 type is displayed on the digital display.
PV
SV
32. Select contact input signal 1 type from the table below with [] key or [] key, and
confirm by pressing “SEL”.
Table 5.21-17 List of set value
Set value Explanation
Initial value
(Default setting)
Setting/checking are not available if the
setting of contact input signal 1 is OFF.
Alternate signal
Momentary signal
6
6Used when the setting of the contact input 1 is “Operation stop signal input”.
Contact input signal 1 delay timer of reading Setting and checking
33. Press the [SEL] key once.
The set screen of the contact input signal 1 delay timer of reading is displayed on the
digital display.