HRX-OM-Q026-B
Chapter 5 Display and setting of various functions
HRSH Series 5.21 Communication function
5-77
38. Select contact input signal 2 from the table below with [] key or [] key, and confirm
by pressing “SEL”.
Table 5.21-20 List of set value
Set value Explanation
Initial value
(Default setting)
Without signal input
Run/stop signal input
External switch signal input(N.O. type)
External switch signal input (N.C. type)
Remote signal input
7
7When the setting of the serial protocol is “Simplified communication protocol 2”, “Remote
signal” cannot be set.
Contact input signal 2 type Setting and checking
39. Press the [SEL] key once.
The set screen of contact input signal 2 type is displayed on the digital display.
PV
SV
40. Select contact input signal 2 type from the table below with [] key or [] key, and
confirm by pressing “SEL”.
Table 5.21-21 List of set value
Set value Explanation
Initial value
(Default setting)
Setting/checking are not available if the
setting of contact input signal 1 is OFF.
Alternate signal
Momentary signal
8
8 Can be set when the setting of contact input signal 2 is "Run/Stop signal input" or "Remote signal"
Contact input signal 2 delay timer of reading Setting and checking
41. Press the [SEL] key once.
The set screen of contact input signal 2 delay timer of reading is displayed on the
digital display.
PV
SV