Chapter 5 Display and setting of various functions
5.21 Communication function HRSH Series
5-78
42. Select contact input signal 2 delay timer of reading from the table below with [] key or
[] key, and confirm by pressing “SEL”.
Table 5.21-22 List of set value
Set value Explanation
Initial value
(Default setting)
Setting and checking are not available unless
contact input signal 2 is external switch signal
input (N.O. type or N.C. type).
to
Setting of contact input signal 2 delay timer of
reading.
Set range is 0 to 300 sec.
Contact input signal 2 OFF detection timer Setting and checking
43. Press the [SEL] key once.
The set screen of contact input signal 2 OFF detection timer is displayed on the digital
display.
PV
SV
44. Select contact input signal 2 OFF detection timer from the table below with [] key or
[] key, and confirm by pressing “SEL”.
Table 5.21-23 List of set value
Set value Explanation
Initial value
(Default setting)
Setting and checking are not available unless
contact input signal 2 is external switch signal
input (N.O. type or N.C. type).
to
Setting of contact input signal 2 OFF
detection timer
Set range is 0 to 10sec.
Contact output signal 1 function Setting and checking
45. Press the [SEL] key once.
The set screen of contact output signal 1 function is displayed on the digital display.
PV
SV