-28-
No.SFOD-OMT0006-F
(2) Stop (relay contact (1))
If the system where this controller is installed has a stop circuit for the whole system, or if the system
has multiple controllers with individual power supply, relay contacts should be made between the
24VDC controller power supply and the EMG terminal of the power supply plug.
Caution
When shutdown is input, the controller stops with maximum deceleration, then the motor is turned
OFF.
(Circuit example)
24VDC
Ry
0V
Stop
Switch
Surge suppressor
The stop is
released switch
Ry: Relay
U
Power supply plug 1
LK RLS (6)
Ry
(1) C 24V
(2) M 24V
0V (4)
(3) EMG
Controller
Input power
supply
DC24V
0V
Power supply plug 2
Power supply plug 3
LK RLS (6)
Ry
(1) C 24V
(2) M 24V
0V (4)
(3) EMG
Controller
Input power
supply
DC24V
0V
LK RLS (6)
Ry
(1) C 24V
(2) M 24V
0V (4)
(3) EMG
Controller
Input power
supply
DC24V
0V