Example:   
The initial position: 50mm 
↓ 
Operation of step data No.1: Position: 200mm, Area1-Area2: 150-250mm 
↓ 
Operation of step data No.2: Position: 100mm, Area1-Area2: 130-170mm 
(7) Area output 
-Procedures-                                                    -Timing chart Area output - 
● Operation of Step Data No.1 
1) Input step data No. (IN0 to IN5). 
↓ 
2) DRIVE is turned ON. 
→ Receive the step data no.1 
(From the input IN0 to IN5). 
Then,  if  the  DRIVE  is  turned  OFF,  the 
step data will be output (from the output 
OUT0 to OUT5). 
↓ 
3) BUSY is turned ON. 
(The electric actuator starts the operation). 
INP is turned OFF. 
↓ 
4) AREA output is turned ON for the step 
data  no.1  (at  150mm  from  the  origin 
point). 
↓ 
5) BUSY is turned OFF. (The electric actuator stops.) 
INP is turned ON. 
↓ 
● Operation of Step Data No.2 
6) Input step data No. (IN0 to IN5). 
↓ 
7) DRIVE is turned ON. 
→ Receive the step data no.2 (from the input IN0 to IN5). 
Then, if the DRIVE is turned OFF, the step data will be output (from the output OUT0 to OUT5). 
↓ 
8) AREA is turned OFF. 
BUSY is turned ON. (The electric actuator starts the operation.) 
↓ 
9) AREA output is turned ON for the step data no.2 (at 170mm from the origin point). 
↓ 
10) AREA output is turned  OFF for the step data no.2 (at 130mm from the origin point). 
↓ 
11) BUSY is turned OFF. (The electric actuator stops.) 
INP is turned ON.   
If the now position is inside of 1 
and  2  area scope  for step  data. 
The AREA signal is ON. 
Otherwise, the signal is OFF 
If the now position is inside of step 
data positioning. The INP signal is 
ON. Otherwise, the signal is OFF.