■Error indication
Flow exceeding the upper limit of the set
flow range is applied.
Flow exceeding the lower limit of the set
flow range is applied.
Ensure the flow is in the
correct direction.
The load current applied to the switch
output has exceeded the maximum
value. (OUT1)
Turn the power off and
remove the cause of the over
current. Then turn the power
on again.
The load current applied to the switch
output has exceeded the maximum
value. (OUT2)
During zero clear operation, pressure
greater than ±5% F.S. is applied.
(The mode is returned to measurement
mode automatically 1 second later).
Retry the zero clear
operation without applying
fluid.
An internal data error has occurred.
Turn the power off and turn it
on again.
Accumulated flow
error
1
Accumulated flow is
displayed
(flashing)
The accumulated flow has exceeded the
accumulated flow range.
(For accumulated increment)
Reset the accumulated flow.
(Press the UP and DOWN
buttons simultaneously for
1 second or longer)
(page 56)
Accumulated flow is
displayed
(flashing)
The accumulated flow has reached the
set accumulated flow.
(For accumulated decrement)
1: A decimal point will be displayed depending on the flow range or measurement unit setting.
: If the error cannot be reset after the above measures are taken, or errors other than above are displayed, please contact SMC.