l LEDs:threeLEDsindicate,bycolorandstate(on/off/blinking
1
/flickering
2
/alternating
3
),different
systeminformation,suchaserrorsorperformanceindications.
Generally,themainLEDindicationsare:
l BlueON-theinverteriscommunicatingwiththemonitoringplatform
l GreenON-thesystemisproducing
l Greenblinking-ACisconnectedbutthesystemisnotproducing
l RedON-systemerror
Figure 12: LEDs
ThefollowingtabledescribessystemperformanceinformationbyLEDcolorandON/OFF/Pswitch
position.
Indication
ON/ OFF/ P
switch
position
LED color
Comment
Red Green Blue
Power optimisers not
paired
ON (1)
OFF Blinking
o
S_OK: ON
o
No S_OK: OFF
S_OK: ON
communication
with the
monitoring
platform is
established
Pairing Blinking Blinking Blinking
Wake-up/ Grid
Monitoring
OFF Blinking Blinking
System Producing OFF ON
o
S_OK: ON
o
No S_OK: OFF
Night mode
(no production)
OFF Flickering
o
S_OK: ON
o
No S_OK: OFF
Inverter is OFF
(Safe DC)
OFF (0)
OFF Blinking
Inverter is OFF
(DC not safe)
Blinking Blinking
o
S_OK: ON
o
No S_OK: OFF
Inverter
configuration
or reboot
ON / P ON ON ON
1
Blinking = Turns ON and OFF for the same duration
2
Flickering = Turns ON for 100 mS and turns OFF for 5 seconds
3
Alternating = Alternate LEDs flash
-Three Phase Inverter with Synergy Technology Installation MAN-01-00402-1.4
24
Primary Unit Interface