91
Country setting "Germany"
Menu Setting Description
System power ≤ 3.68 kVA The maximum plant system rating is 3.68 kVA.
> 3.68 – 13.8kVA The plant system rating is higher than 3.68 kVA
and/or does not exceed 13.8 kVA.
> 13.8 kVA – 30 kVA The plant system rating is higher than 13.8 kVA
and/or does not exceed 30 kVA.
> 30 kVA The plant system rating is higher than 30 kVA.
An external grid monitoring and remote shut-
down will be used.
I/O module
1)
Inactive The function for the external shutdown is
deactivated (EISD-ENA status: Disabled).
On The function for the external shutdown is
activated (EISD-ENA status: Enabled).
CosPhi(Pac) - QMCPP Inactive
The "cosφ(Pac)" function is deactivated (no
reactive power feed-in, cosφ=1).
On
The "cosφ(Pac)" function for the feed-in / input
of reactive power is activated.
1)
the menu is only displayed when the optional I/O module has been tted.
Country setting "Great Britain"
Menu Setting Description
System power ≤ 16 A per phase The output current is max. 16 A (inverter
settings in accordance with standard G83/2;
available only for SM2000P, SM3000P and
SM4000P.)
> 16 A per phase The output current is greater than 16 A (inverter
settings in accordance with standard G59/2;
available only for SM4000P, SM4600P and
SM5000P).
Country setting "Italy"
Menu Setting Description
System power ≤ 3 kW The maximum plant system rating is 3 kW.
> 3 kW – 6 kW The plant system rating is higher than 3 kW
and/or does not exceed 6 kW.
I/O module
1)
Inactive Remote control of the inverter via SPI logic is
deactivated (SPIL-ENA status: Disabled).
On Remote control of the inverter via SPI logic is
activated (SPIL-ENA status: Enabled).
1)
the menu is only displayed when the optional I/O module has been tted.