en
113
Status message Cause Actions
Frequency too high The mains frequency is outside
the GFMMAX1-THR, GFMMAX2-
THR or GPTFMAX-THR limit
values.
If this problem recurs, contact
the grid operator in charge.
Frequency too low The mains frequency is outside
the GFMMIN1-THR, GFMMIN2-
THR or GPTFMIN-THR limit values.
Mains error The inverter detects island mode. If this problem recurs, contact
the grid operator in charge.
Vac too high The mains voltage is outside the
GVMMA X1-THR, GVMMAX2-THR
or GPTVMAX-THR limit values.
If this problem recurs, contact
the grid operator in charge.
Vac too low The mains voltage is outside the
GVMMIN1-THR, GVMMIN2-THR or
GPTVMIN-THR limit values.
Vac 10 min too high The maximum 10-minute average
value of the mains voltage
GVM10AMAX-THR is too high.
Insulation fault DC The insulation resistance of the PV
generator to ground is too low.
Check the PV generator.
Phase and neutral conductor are
interchanged.
Connect the AC supply
conductors as described in
section 5.3.
Error ext. input 1 The external grid monitoring (NA
protection / Teledistacco) has
disconnected the inverter from the
grid. An active signal is present at
the "NA" input (external shutdown)
of the I/O module.
If this problem recurs, contact
the grid operator in charge.
8.2.4 Error
The status LED lights up red.
Status message Cause Actions
Device error (+ error code) The inverter is defective. Note the displayed two-digit
error code and contact the
SolarMax Service Center.