28
Country setting “Denmark”
Menu Setting Description
Plant type
≤ 13.8 kVA
The maximum plant system rating is 13.8 kVA.
> 13.8 kVA – ≤ 30 kVA
The plant system rating is higher than 13.8 kVA
and/or does not exceed 30 kVA.
> 30 kVA
The plant system rating is higher than 30 kVA.
Country setting “Germany”
Menu Setting Description
Grid connection Medium voltage
The inverter is connected to the medium-
voltage mains.
Low voltage
The inverter is connected to the low-voltage
mains.
Plant type*
< 13.8kVA The plant system rating is lower than 13.8 kVA.
13.8–30kVA The plant system rating is between 13.8 kVA
and 30kVA.
> 30 kVA The plant system rating is higher than 30 kVA.
An external grid monitoring and remote shut-
down will be used.
VDE 0126-1-1 Required setting if the inverter is commissioned
within a PV plant connected to the grid before 1
January 2012. Note: The setting “VDE 0126-1-
1” is inadmissible for PV plants connected to the
grid after 31 December 2011.
cosφ(Pac)
Inactive
No reactive power feed-in (cosφ=1)
On
Standardised reactive power feed-in
* the menu is only displayed at the “Low-voltage” grid connection.