Function / Parameter Description Unit
- Vac Lock-In Low Lower value at which the reactive power mode "Q(Vac)
mode 2" is activated.
V
- QR 2 Fixed reactive power in reactive power mode "Q(Vac)
mode 2" (when grid voltage is too low; in % of
Pac nom)
%
- Pac Lock Active power-dependent on/off switch for the reactive
power modes cosφ and Q.
Inactive/
on
- Pac Lock-In Value at which the reactive power mode is activated. W
- Pac Lock-Out Value at which the reactive power mode is deactivated
(cosφ =1).
W
FRT Fault ride through function for dynamic grid support Inactive/
on
- K-Factor Reactive current static factor for voltage support with
reactive current during mains drops
-
Iac max Maximum admissible mains current (per phase) A
Pac max Maximum effective power to be fed W
S max Maximum apparent power to be fed. VA
6.8 Settings
This menu can be used to set different communication parameters and monitoring func-
tions. All settings can also be implemented with MaxTalk.
Parameter Description
Language Selection of the display language (German, English, French, Italian, or
Spanish). The display language can be selected independently of the
selected specic country settings.
Time Setting the internal clock
Date Setting the displayed date
Device address Denition of the device address between 1 and 249. If you connect
several inverters and accessory components to become one MaxComm
communication network, each device within the network must have an
individual address.
IP
Conguration of the Ethernet interface. Details see Section 5.3.Netmask
TCP Port
Status relay delay Setting the switching delay of the status signalling contact
Pinst tot Rated output of the PV generator (entry only possible in MaxTalk).