108
Operation on LCD
NOTICE!
If the ambient temperature is extremely low, turning on battery heating will consume
a significant amount of electrical energy.
Setting Extend BAT FUNC
This function allows for adding a new battery module to an existing system. It is only
applicable and functional in on-grid mode and cannot be used in EPS (off-grid) mode.
In on-grid mode, enabling this function will make the inverter to charge or discharge the
battery SOC to approximately 40%. This function will turn to Disable automatically after 48
hours this function enabled.
===Extend BAT FUNC===
Function Control
> Enable <
Setting HotStandby Settting
This function is mainly to reduce the energy losses of the system when the power of load
is very low.
Enable: When the power of load is very low and other conditions for entering
hot standby are met, the inverter will enter HotStandby status to reduce system
losses.
Disabled: Even when the power of load is very low and other conditions for
entering hot standby are met, the inverter will not enter HotStandby status and
continue to output power to the load. It is disabled by default.
===HotStandby Setting===
Function Control
> Enable <
Setting Pgrid Bias
This function is disabled by default.
When the inverter has no power output:
a. Check the Meter/CT value in Menu>System Status>Meter/CT when the function
is disabled.
Disable: disabling this function
Grid: The inverter will discharge more energy to the grid.
INV: The inveter will be biased to charge power from the grid.