Troubleshooting and Maintenance
Error Code Fault Diagnosis and Solutions
IE 109 Meter Fault Meter fault
Check if the meter is normal and is compatible
with the inverter.
Check if the communication cable is normal and
properly connected.
Check if the communication settings such as
protocol, address and baud rate of the meter are
consistent with those of the inverter.
Contact SolaX for help if it can not return to
normal.
IE 110 BypassRelayFlt Bypass relay fault
Press the ESC key to restart the inverter.
Contact SolaX for help if it can not return to
normal.
IE 111 ARMParaComFIt ARM parameter communication fault
Check that the communication cables of inverters
are well connected and the baud rate of COMM
setting of inverters are the same.
Contact SolaX for help if it can not return to
normal.
IE 112 FAN1 Fault FAN1 fault
Check if the foreign objects stuck in the fan.
Change the fan.
Contact SolaX for help.
IE113 FAN2 Fault FAN2 fault
Check if the foreign objects stuck in the fan.
Change the fan.
Contact SolaX for help.
BE 01 BMS_Exter_Err
Battery error - external communication fault
Contact the battery supplier for help.
BE 02 BMS_InterErr
Battery error - internal communication fault
Contact the battery supplier for help.
BE 03 BMS_OverVolt
Over voltage in battery system
Contact the battery supplier for help.
BE 04 BMS_LowerVolt
Low voltage in battery system
Contact the battery supplier for help.
BE 05 BMS_ChargeOCP
Battery fault - over charge fault
Contact the battery supplier for help.
BE 06 DischargeOCP
Battery fault-discharge over current fault
Contact the battery supplier for help.