45
Electrical Connection
etc., ensure that their start power does not exceed the EPS (off-grid) peak
power of the inverter.
Table 8-4 EPS (off-grid) load information
Type of load Equipment Start power
Resistive load
Lamp Rated power
Fan Rated power
Hair dryer Rated power
Inductive load
Refrigerator 3-5 times rated power
Air conditioner 3-6 times rated power
Washing machine 3-5 times rated power
Microwave oven 3-5 times rated power
* Refer to the nominal start power of the equipment for the actual start power. The EPS
(off-grid) terminal of the inverter does not support a half-wave load to be connected.
Wiring procedures
Step 1: Prepare Grid cable and EPS (off-grid) cable (see "5.3 Additionally Required
Materials" for cable requirement) and strip off the insulation of the conductor to
an appropriate length.
Five-core cable for grid connection
55-60 mm
12 mm
Figure 8-8 Stripping the Grid cable
Four-core cable for EPS (off-grid) connection
55-60 mm
12 mm