Electrical Connection
Step 5: Insert the crimped conductors L1, L2, L3, N, and grounding conductor into
the terminal block according to the labeling and tighten the terminal block
screws (torque: 2.0 ± 0.1 N·m). Insert the ferrite core and terminal block into the
connector enclosure and tighten the swivel nut clockwise.
1
2
3
Click!
Figure 7-12 Assembling the AC connector
Step 6: Remove the AC terminal caps and plug the assembled AC connectors into Grid
terminal and EPS terminal correspondingly.
Click!
Figure 7-13 Installing the AC connector to inverter
WARNING!
Reinstall AC termincal caps immediately after removing the connectors from
terminals.