EasyManua.ls Logo

Sonel MPI-536 - Phase Sequence; Motor Rotation

Sonel MPI-536
144 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MPI-536 USER MANUAL
134
Measuring ranges of LP-10B probe
Range
[lx]
Resolution
[lx]
Spectral
uncertainty
Accuracy
0...39.99
0.01
f1<6%
(5% m.v. + 5 digits)
40.0...399.9
0.1
400...3999
1
4.00 k…39.99 k
0.01 k
40.0 k…399.9 k
0.1 k
Range
[fc]
Resolution
[fc]
Spectral
uncertainty
Accuracy
0...3.999
0.001
f1<6%
(5% m.v. + 5 digits)
4.00...39.99
0.01
40.0...399.9
0.1
400...3999
1
4.00 k…39.99 k
0.01 k
Probe class B
Measuring ranges of LP-10A probe
Range
[lx]
Resolution
[lx]
Spectral
uncertainty
Accuracy
0...3.999
0.001
f1<2%
(2% m.v. + 5 digits)
4.00...39.99
0.01
40.0...399.9
0.1
400...3999
1
4.00 k…39.99 k
0.01 k
40.0 k…399.9 k
0.1 k
Range
[fc]
Resolution
[fc]
Spectral
uncertainty
Accuracy
0...3.999
0.001
f1<2%
(2% m.v. + 5 digits)
4.00...39.99
0.01
40.0...399.9
0.1
400...3999
1
4.00 k…39.99 k
0.01 k
Probe class A
10.1.10 Phase sequence
Phase sequence indication: in the same direction (correct), opposite direction (incorrect)
Range of network voltages U
L-L
: 95 V...500 V (45 Hz…65 Hz)
Display of phase-to-phase voltages
10.1.11 Motor rotation
EMF motor voltage ranges: 1 V ÷ 500 V AC
Test current (per phase): <3.5 mA

Table of Contents

Related product manuals