MPI-536 USER MANUAL
83
3.10.2 Measurement using probes
WARNING
During measurements of insulation resistance, dangerous voltage up to 1 kV
occurs at the ends of test leads of the meter.
It is forbidden to disconnect test leads before the measurement is completed.
Failure to obey the above instruction will lead to electric shock with high volt-
age and make it impossible to discharge the tested object.
Select item R
ISO
to call up the
measurement menu.
Connect the probes to the me-
ter.
Enter the measurement settings in accordance with section 3.10.1
Connect test leads to the measured object.