Frequency Inverter ST600 Series High-Performance Multifunction VFD Basic Operation Instructions
-117-
Control short-term vibration: If the vibration cycle is short is almost the same as the set value of
derivative time (Td), it indicates derivative action is too strong, shorten the derivative time (Td) to
control vibration. When derivative time (Td) is set to 0.00 (namely no derivative control), and there is
no way to control vibration, decrease the proportional gain.
Before adjustment
After adjustment
Response
Time t
0: Set by P09.01
1: AI1
2: AI2
3: AI3
4: High-speed pulse HDIA
5: Multi-step
6: Modbus/Modbus TCP communication
7: PROFIBUS/CANopen/DeviceNet
communication
8: Ethernet communication
9: High-speed pulse HDIB
10: EtherCAT/PROFITNET/EtherNet IP
communication
11: Programmable expansion card
12: Reserved
0: AI1
1: AI2
2: AI3
3: High-speed pulse HDIA
4: Modbus/Modbus TCP communication
5: PROFIBUS/CANopen/DeviceNet
communication
6: Ethernet communication
7: High-speed pulse HDIB
8: EtherCAT/PROFITNET/Ethernet IP
communication
9: Programmable expansion card