Frequency Inverter ST600 Series High-Performance Multifunction VFD Function parameter list
-175-
Deceleration time
of jogging
Jogging deceleration time is the time needed from
decelerating from the max. output frequency (P00.03) to
0Hz.
Setting range: 0.0–3600.0s
When the set frequency is within the range of jump
frequency, the VFD will run at the boundary of jump
frequency.
The VFD can avoid mechanical resonance point by
setting the jump frequency, and three jump frequency
points can be set. If the jump frequency points are set to
0, this function will be invalid.
Set frequency f
Time t
Jump
frequency 2
1/2* jump amplitude 2
1/2* jump amplitude 2
Jump
frequency 1
1/2* jump amplitude 1
1/2* jump amplitude 1
Jump
frequency 3
1/2* jump amplitude 3
1/2* jump amplitude 3
Setting range: 0.00Hz–P00.03 (max. output frequency)
Jump frequency
amplitude 1
Jump frequency
amplitude 2
Jump frequency
amplitude 3
Amplitude of
wobbling
frequency
0.0–100.0% (relative to set frequency)
Amplitude of jump
frequency
0.0–50.0% (relative to amplitude of wobbling frequency)
Rise time of
wobbling
frequency
Descend time of
wobbling
frequency
Switching
frequency of
acceleration/decel
eration time
0.00–P00.03 (max. output frequency)
0.00Hz: no switch-over
Switch to acceleration/deceleration time 2 if the running
frequency is larger than P08.19
Frequency
threshold of the
start of droop
control
Reference
frequency of
acceleration/decel
eration time
0: Max. output frequency
1: Set frequency
2: 100Hz
Note: Valid for straight acceleration/deceleration only.