These function codes define the relation between analog
input voltage and corresponding set value of analog
input. When the analog input voltage exceeds the range
of max./min. input, the max. input or min. input will be
adopted during calculation.
When analog input is current input, 0–20mA current
corresponds to 0–10V voltage.
In different application cases, 100% of the analog setting
corresponds to different nominal values.
The figure below illustrates several settings.
Input filter time: Adjust the sensitivity of analog input,
increase this value properly can enhance the anti-
interference capacity of analog variables; however, it will
also degrade the sensitivity of analog input.
Note: AI3 and AI4 can support 0–10V/0–20mA input,
when AI3 and AI4 select 0–20mA input, the
corresponding voltage of 20mA is 10V;
Setting range of P25.24: 0.00V–P25.26
Setting range of P25.25: -300.0%–300.0%
Setting range of P25.26: P25.24–10.00V
Setting range of P25.27: -300.0%–300.0%
Setting range of P25.28: 0.000s–10.000s
Setting range of P25.29: 0.00V–P25.31