Frequency Inverter ST600 Series High-Performance Multifunction VFD Basic Operation Instructions
-69-
P04.10
Low-frequency oscillation
control factor of motor 1
0–100
10
P04.11
High-frequency oscillation
control factor of motor 1
0–100
10
P04.12
Oscillation control threshold
of motor 1
0.00Hz–P00.03 (max. output frequency)
30.00Hz
P04.13
V/F curve setup of motor 2
0: Straight V/F curve;
1: Multi-point V/F curve
2: Torque-down V/F curve (power of 1.3)
3: Torque-down V/F curve (power of 1.7)
4: Torque-down V/F curve (power of 2.0)
5: Customize V/F (V/F separation)
0
P04.14
Torque boost of motor 2
0.0%: (automatic) 0.1%–10.0%
0.0%
P04.15
Motor 2 torque boost cut-off
0.0%–50.0% (rated frequency of motor 1)
20.0%
P04.16
V/F frequency point 1 of
motor 2
0.00Hz–P04.18
0.00Hz
P04.17
V/F voltage point 1 of motor 2
0.0%–110.0%
0.0%
P04.18
V/F frequency point 2 of
motor 2
P04.16– P04.20
0.00Hz
P04.19
V/F voltage point 2 of motor 2
0.0%–110.0%
0.0%
P04.20
V/F frequency point 3 of
motor 2
P04.18– P02.02 or P04.18– P02.16
0.00Hz
P04.21
V/F voltage point 3 of motor 2
0.0%–110.0%
0.0%
P04.22
V/F slip compensation gain of
motor 2
0.0–200.0%
100.0%
P04.23
Low-frequency oscillation
control factor of motor 2
0–100
10
P04.24
High-frequency oscillation
control factor of motor 2
0–100
10
P04.25
Oscillation control threshold
of motor 2
0.00Hz–P00.03 (max. output frequency)
30.00Hz
P04.26
Energy-saving run
0: No
1: Automatic energy-saving run
0