Frequency Inverter ST600 Series High-Performance Multifunction VFD Basic Operation Instructions
-70-
P04.27
Channel of voltage setup
0: Keypad; output voltage is determined by
P04.28
1: AI1
2: AI2
3: AI3
4: HDIA
5: Multi-step
6: PID
7: Modbus/Modbus TCP communication
8: PROFIBUS/CANopen communication
9: Ethernet communication
10: HDIB
11: EtherCAT/PROFITNET/Ethernet IP
communication
12: PLC card
13: Reserved
0
P04.28
Set voltage value via keypad
0.0%–100.0% (rated motor voltage)
100.0%
P04.29
Voltage acceleration time
0.0–3600.0s
5.0s
P04.30
Voltage deceleration time
0.0–3600.0s
5.0s
P04.31
Max. output voltage
P04.32100.0% (rated motor voltage)
100.0%
P04.32
Min. output voltage
0.0%P04.31 (rated motor voltage)
0.0%
P04.33
Flux-weakening coefficient in
the constant power zone
1.001.30
1.00
P04.34
Injection current 1 in
synchronous motor VF
control
When the synchronous motor VF control mode
is enabled, this parameter is used to set the
reactive current of the motor when the output
frequency is lower than the frequency set in
P04.36.
Setting range: -100.0%+100.0% (of the motor
rated current)
20.0%
P04.35
Injection current 2 in
synchronous motor VF
control
When the synchronous motor VF control mode
is enabled, this parameter is used to set the
reactive current of the motor when the output
frequency is higher than the frequency set in
P04.36.
Setting range: -100.0%+100.0% (of the motor
rated current)
10.0%