Frequency Inverter ST600 Series High-Performance Multifunction VFD Basic Operation Instructions
-89-
Note: "/" indicates this multi-function terminal is invalid under present reference channel.
When setting the auxiliary frequency inside the VFD via multi-function terminal UP (10) and DOWN
(11), users can increase/decrease the frequency quickly by setting P08.45 (UP terminal frequency
incremental change rate) and P08.46 (DOWN terminal frequency decremental change rate).
Sx
Sy
UP terminal
function selection=10
DOWN terminal
function selection=11
UP terminal state
DOWN terminal state
T
F
T
T
UP terminal frequency incremental integral speed P08.45
DOWN terminal frequency decremental integral speed P08.46
Related parameter list:
Function
code
Name
Description
Default
value
P00.03
Max. output frequency
P00.04–400.00Hz
50.00Hz
P00.04
Upper limit of running
frequency
P00.05–P00.03
50.00Hz
P00.05
Lower limit of running
frequency
0.00Hz–P00.04
0.00Hz
P00.06
A frequency command
selection
0: Set via keypad
1: Set via AI1
2: Set via AI2
3: Set via AI3
4: Set via high speed pulse HDIA
5: Set via simple PLC program
6: Set via multi-step speed running
7: Set via PID control
8: Set via Modbus/Modbus TCP
communication
9: Set via PROFIBUS/CANopen/ DeviceNet
communication
10: Set via Ethernet communication
11: Set via high speed pulse HDIB
12: Set via pulse train AB
13: Set via EtherCAT/PROFITNET/Ethernet
IP communication
14: Set via PLC card
15: Reserved
0
P00.07
B frequency command
selection
15