Frequency Inverter ST600 Series High-Performance Multifunction VFD Basic Operation Instructions
-90-
Reference object of B
frequency command
0: Max. output frequency
1: A frequency command
Combination mode of setup
source
0: A
1: B
2: (A+B)
3: (A-B)
4: Max (A, B)
5: Min (A, B)
Function of multi-function
digital input terminal (S1–S4,
HDIA, HDIB)
10: Frequency increase (UP)
11: Frequency decrease (DOWN)
12: Clear frequency increase/decrease setting
13: Switch-over between setup A and setup B
14: Switch-over between combination setup
and setup A
15: Switch-over between combination setup
and setup B
0x000–0x221
Ones: Frequency enabling selection
0: UP/DOWN terminal setting is valid
1: UP/DOWN terminal setting is invalid
Tens: Frequency control selection
0: Valid only when P00.06=0 or P00.07=0
1: Valid for all frequency modes
2: Invalid for multi-step speed when multi-step
speed takes priority
Hundreds: Action selection at stop
0: Valid
1: Valid during running, clear after stop
2: Valid during running, clear after receiving
stop command
UP terminal frequency
incremental change rate
DOWN terminal frequency
decremental change rate
0.00Hz–P00.03 (max. output frequency)
Ramps reference frequency
0.00Hz–P00.03 (max. output frequency)