SINGLE PHASE HI 10/12kW | User Manual23
If the CT coil is tted in the wrong way
then this variable will have negative
instead of positive values when the
power is owing into the
house/inverter. Also, the inverter
export limiting function will not work
properly.
The primary side of the CT
needs to be clamped on the
Grid live line.
If the data read by the CT is wrong, you can try to point
the direction of the CT to the grid.
Inverter
N L
White wire
3 4
Black wire
Grid
L
N
CT
3
4
CT
Arrow pointing
to inverter