EasyManua.ls Logo

SunSynk SUNSYNK-10K-SG02LP1 - GRID POWER FACTOR CONTROL; Reactive Power (P(Q)) and PF Settings

SunSynk SUNSYNK-10K-SG02LP1
79 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINGLE PHASE HI 10/12kW | User Manual57
What this page displays:
P(Q): It adjusts the inverter reactive power according to the set active power.
P(PF): It adjusts the inverter PF according to the set active power.
Lock-in/Pn 50%: When the inverter output active power is less than 50% rated power, it won't enter the
P(PF) mode.
Lock-out/Pn 50%: When the inverter output active power is higher then 50% rated power, it will enter
the P(PF) mode.
For the detailed setup values, please follow the local grid code.
NOTE:
Only when the grid voltage is equal to or higher than 1.05 times the rated grid voltage will the P(PF)
mode take eect.




 

 


 


















Table of Contents

Related product manuals