TAC AB, 1998-10-23 0-004-7614-0 (GB), App:5 (6)
TAC 2413 Handbook Commissioning protocol/List of parameters
P No. Parameter Min. Max. Step Default Change Comment
P 66 P band, holding controller 1 °C 400 °C 0,1 °C 200 °C
P 67 I time, holding controller 1 min 20 min 1 min 4 min
P 68 P band, supply air control 1 °C 100 °C 0,1 °C 25 °C
during cooling control
P 69 I time, supply air control 1 min 20 min 1 min 4 min
during cooling control
P 70 Gain, room controller 1 20 0,1 2 °C/°C
P 71 I time , room controller 1 min 60 min 1 min 20 min
P 72 Fan alarm tripped A alarm or B alarm (60 sec)
P 73 Frost protection alarm tripped A alarm (5 sec)
P 74 Faulty sensor, frost pr. tripped A alarm (5 sec)
P 75 Pump alarm heating c. tripped A alarm (5 sec)
P 76 Alarm for battery A alarm (5 sec)
overheating tripped
P 77 Freezing alarm tripped A alarm (30 min)
P 78 Fire alarm tripped A alarm or B alarm (60 sec)
P 79 Efficiency alarm tripped A alarm or B alarm (60 min)
P 80 Deviation alarm tripped A alarm or B alarm (60 min)
P 81 Fan alarm, choice of type 0 0=B alarm, 1=B alarm+Sum, 2=A alarm
P 82 Fire alarm, choice of type 2 0=B alarm, 1=B alarm+Sum, 2=A alarm
P 83 Efficiency alarm, choice 0 0=B alarm, 1=B alarm+Sum, 2=A alarm
of alarm type
P 84 Efficiency alarm, alarm limit 0 % 100 % 1 % 50 %
P 85 Deviation alarm 0 (0=disabled, 1=active) summer per.
P 86 Deviation alarm, type choice 0 0=B alarm, 1=B alarm+Sum, 2=A alarm
P 87 Deviation alarm, alarm limit 0 °C 20 °C 0,1 °C 3 °C positive or negative deviation
P 88 Manual control, alarm choice 0 0=no sum, 1=sum alarm
P 89 Room sensor adjustment –5 °C 5 °C 0,1 °C 0 °C
P 90 Outd. temp. block 1/1 speed –50 °C 20 °C 0,1 °C –50 °C
P 91 FF stop during night heating 0 1=TF in operation only
P 92 Neutral zone, supply air cont. 5 20 1 5 x0,1 (5=0,5°C)
P 93 SPC/CO
2 input signal 0V 10V 0,1 Measured value
P 94 ---
P 95 ---
P 96 Clock 00:00 Setting
P 97 Date 01.01 Setting
P 98 Year 1998
P 99 Version. Type of controller
and program version
P -- Cold start. First, press the Complete reset. All parameters
plus button, then press the will assume their factory set values.
enter button.