127
SYSTem:PRELoad[:STATe] <Bool>
Function Enables / Disables Preload.
If disabled, preload is deactivated 5 seconds after DC output off.
Parameters
0|1, OFF|ON
Query
SYSTem:PRELoad[:STATe]?
Return
<Bool> 0|1
SYSTem:PSOK:DELay <NRf+>
Function
Set PS_OK signal delay following output ON.
Parameters
0.000 ~ 10|MIN|MAX. Resolution: 0.001
Unit
S
Query SYSTem:PSOK:DELay?
SYSTem:PSOK:DELay? MAX
SYSTem:PSOK:DELay? MIN
Return
<NRf>
SYSTem:RANGe <DSC>
Function Sets the Power Supply analog programming & monitor range.
Programming – 5/10 Volts or 5/10kΩ.
Monitoring 5/10 Volts.
Parameters
5|10
Query
SYSTem:RANGe?
Return
<DSC> 5|10
SYSTem:RIN[:LEVel] <NRf+>
Function
Sets the internal resistance value.
Parameters
0…1|MIN|MAX. Resolution: 0.001
Unit
Query SYSTem:RIN[:LEVel]?
SYSTem:RIN[:LEVel]? MAX
SYSTem:RIN[:LEVel]? MIN
Return
<NRf> “x.xxx”
SYSTem:RIN:STATe <Bool>
Function
Enables / Disables the internal resistance function.
Parameters
0|1, OFF|ON
Query
SYSTem:RIN:STATe?
Return
<Bool> 0|1
NOTE:
The Internal Resistance function can be set to ON only if the Sequencer, Constant Power Limit,
Analog Programming and Slew-Rate modes are disabled.