EasyManua.ls Logo

TDK-Lambda Z+ series - Measure Subsystem; Display Subsystem

TDK-Lambda Z+ series
138 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
100
7.12.5 Measure Subsystem
This subsystem reads the actual voltage and current. The power is a result of multiplying voltage
and current measurements.
MEASure
:CURRent[:DC]?
:VOLTage[:DC]?
:POWer[:DC]?
MEASure:CURR?
Reads the measured output current. Returns a 5 digit string.
SCPI Command Syntax MEASure:CURRent?
GEN Command Syntax MC?
Parameters None
Default Suffix A
Returned Parameters <NR3>
MEASure:VOLTage?
Reads the measured output voltage. Returns a 5 digit string.
SCPI Command Syntax MEASure:VOLTage?
GEN Command Syntax MV?
Parameters None
Default Suffix V
Returned Parameters <NR3>
MEASure:POWer?
Reads the measured output power. Returns a 5 digit string.
SCPI Command Syntax MEASure:POWer?
GEN Command Syntax MP?
Parameters None
Default Suffix W
Returned Parameters <NR3>
7.12.6 DISPlay Subsystem
DISPlay
[:WINDow]:STATus <bool> Display ON/OFF
[:WINDow]:FLASh <bool> Display Flash

Table of Contents

Related product manuals