88
*ESE
Standard Event Status Enable command. Modifies the contents of the Event Status Enable Register.
Meaning and Type Event Status Enable Device Status
Command Syntax *ESE <NRf>
Parameters 0 to 255
Power On Value 1
Query Syntax *ESE?
Parameters <NR1> 3digits
Query Syntax *ESR? *PSC *STB?
Bit Position 7 6 5 4 3 2 1 0
Bit Name PON 0 CME EXE DDE QYE 0 OPC
Bit Weight 128 64 32 16 8 4 2 1
CME = Command error; DDE = Device-dependent error; EXE = Execution error; OPC = Operation,
complete; PON Power-on; QYE = Query error
*ESR?
Standard Event Status Register query. Returns the contents of the Event Status Register.
Meaning and Type Event Status Device Status
Query Syntax *ESR?
Parameters None
Returned Parameters <NR1> (Register binary value) format 3 digits
*IDN?
Identification query. Returns an identification string in the following format: ‘Manufacturer, Model,
Serial number, Firmware level’.
Meaning and Type Identification System Interface
Query Syntax *IDN?
Returned Parameters
Field Information
TDK-Lambda Manufacturer
Z Model
<Vrating>-<Irating> Model ratings
25B1234 Serial number, typically 7 alpha-numeric characters
3.0-C1 Revisions, <Main firmware>–<LAN/IEEE firmware>
Example TDK-Lambda,Z20-30,25B1234, 1.0-C1