TECDrive20-EU Series Inverter Function parameters
-97-
Function
code
Name
Description
Default
Modify
When the function code is set as non-zero, if the
interval time between two communications
exceeds the communication overtime, the
system will report "485 communication faults"
(CE).
P14.05
Transmission
error
processing
0: Alarm and stop freely
1: No alarm and continue running
2: No alarm and stop as per the stop mode (only
under communication control mode)
3: No alarm and stop as per the stop mode
(under all control modes)
0
○
P14.06
Communication
processing
action selection
0x000–0x111
Ones place: Responding to write operations
0: Yes
1: No
Tens place: Communication encryption
0: Disabled
1: Enabled
Hundreds place: User-defined communication
command address
0: Disabled
1: Enabled
0x000
○
P14.07
User-defined
address for
running
commands
0x0000–0xFFFF
0x1000
○
P14.08
User-defined
address for
frequency
setting
0x0000–0xFFFF
0x2000
○
P17 group Status viewing
Function
code
Name
Description
Default
Modify
P17.00
Setting
frequency
Display current set frequency of the inverter
Range: 0.00Hz–P00.03
●
P17.01
Output
frequency
Display current output frequency of the inverter
Range: 0.00Hz–P00.03
●