TECDrive20-EU Series Inverter Function parameters
-97-
When the function code is set as non-zero, if the
interval time between two communications
exceeds the communication overtime, the
system will report "485 communication faults"
(CE).
Transmission
error
processing
0: Alarm and stop freely
1: No alarm and continue running
2: No alarm and stop as per the stop mode (only
under communication control mode)
3: No alarm and stop as per the stop mode
(under all control modes)
Communication
processing
action selection
0x000–0x111
Ones place: Responding to write operations
0: Yes
1: No
Tens place: Communication encryption
0: Disabled
1: Enabled
Hundreds place: User-defined communication
command address
0: Disabled
1: Enabled
User-defined
address for
running
commands
User-defined
address for
frequency
setting
P17 group Status viewing
Display current set frequency of the inverter
Range: 0.00Hz–P00.03
Display current output frequency of the inverter
Range: 0.00Hz–P00.03